Foil tape is bought by the roll and specified by the joint. Three constructions cover most industrial demand, and they are not interchangeable: plain aluminium foil with a rubber or acrylic adhesive, FSK (foil-scrim-kraft) facing tape, and heavy-gauge jacketing with a release liner. Getting the wrong one shows up as a joint that will not hold at temperature, a vapour barrier that tears at the seam, or a duct that fails an inspection.
1. Plain foil tape: sealing and heat reflection
Plain aluminium foil with a rubber adhesive is the general-purpose choice for duct sealing, flexible duct joints and reflective heat shielding. The foil conducts heat away from the joint and reflects radiant heat; the adhesive holds on metal, and on cleaned galvanised or stainless surfaces it is dependable at moderate temperature.
Two limits matter. Rubber adhesive softens above roughly 90–120 °C depending on grade, so high-temperature exhaust work needs an acrylic or silicone system. And foil is thin: on a seam that moves, a 30 µm foil will crack before the adhesive fails.
2. FSK facing tape: closing the vapour barrier
| Construction | What it does | Where it goes |
| Plain aluminium foil | Reflective, vapour tight, conforms to curves | Duct joints, pipe wrapping, heat shielding |
| FSK (foil + fibreglass scrim + kraft) | Reinforced facing, resists tearing at the seam | Insulation board and duct facing, lagging seams |
| Heavy jacketing foil (with liner) | Mechanical protection plus weather barrier | Outdoor duct, chillers, vessel and tank cladding |
FSK exists because plain foil tears where the scrim of the insulation board ends. The fibreglass scrim carries the load; the kraft layer gives the adhesive something to bite. If the specification calls for a vapour barrier on faced insulation, plain foil is the wrong purchase even though it is cheaper per square metre.
3. Jacketing: protection, not sealing
Heavy-gauge foil jacketing is specified for mechanical protection outdoors: chillers, tanks, large duct runs. It is thicker, usually supplied with a release liner so it can be cut and positioned before the adhesive grabs, and it is expected to survive weather and occasional contact rather than to seal a pressure joint.
The failure mode here is almost always the seam, not the field of the tape. Overlap direction, surface temperature at application and whether the substrate was wiped clean decide whether the jacket stays closed through a winter.
Adhesive, not foil, decides temperature
Rubber adhesive: general duct work, moderate service temperature, lowest cost.
Acrylic adhesive: better ageing, higher continuous temperature, preferred outdoors.
Silicone adhesive: highest temperature, used where the joint sees exhaust or process heat.
Ask for the adhesive system and the service temperature separately. A foil tape sold as "high temperature" without naming the adhesive is not a specification.
What we hold
Our foil range covers plain aluminium in several thicknesses, FSK facing tape, and heavy jacketing with liner, in rubber, acrylic and silicone adhesive systems. Standard widths are stocked for slitting; wider jacketing rolls ship from stock.
Frequently asked
Can I use duct foil tape on a flue?
Only with an adhesive rated for the flue temperature. Standard rubber-adhesive duct foil is not a flue product; use a high-temperature grade and confirm the continuous rating.
Why does the tape lift at the seam after a few months outdoors?
Usually application temperature and surface contamination, not the adhesive class. Foil does not stretch, so any movement concentrates at the seam; clean, prime where required, and roll down with pressure.
Do you supply FSK tape in wide rolls?
Yes, and slit to width for facing machines, with RoHS and REACH documentation for export orders.